How to Use This Voltage Drop Calculator
This voltage drop calculator checks NEC compliance for any wire run — enter your system voltage, load current, one-way wire length, wire gauge, and conductor material. The calculator returns the voltage drop in volts, the percentage drop relative to source voltage, and the actual voltage delivered to the load. A color-coded NEC compliance badge shows whether the result is within the 3% branch circuit or 5% total system recommendation. Use this tool before pulling wire on any long circuit run — a few seconds of planning can save you from re-pulling undersized conductors.
What Is Voltage Drop?
Voltage drop is the reduction in electrical potential that occurs as current flows through the resistance of a wire. Every conductor has resistance; when current passes through it, some of the electrical energy is converted to heat, and the voltage at the far end of the wire is lower than at the source. The longer the wire and the higher the current, the greater the drop. In residential wiring, a 120V circuit with 5% voltage drop delivers only 114V to the outlet — enough to dim lights noticeably and stress motors.
Why Voltage Drop Matters
Motors are the most voltage-sensitive common load. A motor rated for 115V but receiving 105V draws more current to maintain torque, which heats the windings and shortens motor life. HVAC systems, power tools, and well pumps are especially susceptible. Sensitive electronics and LED drivers can also malfunction or produce flickering when supply voltage falls outside rated tolerances. Keeping drop within NEC recommendations protects equipment and ensures circuits perform as designed.
The Voltage Drop Formula
The NEC Chapter 9, Table 9 method gives the industry-standard formula for copper and aluminum conductors at 75°C operating temperature.
DC and AC Single-Phase Voltage Drop
V_drop = 2 × L × I × R_per_ft
Where L is the one-way wire length in feet, I is the load current in amps, and R_per_ft is the conductor resistance per foot (Ω/ft). The factor of 2 accounts for both the outgoing and return conductors — current must travel out and back. This formula applies equally to DC circuits and AC single-phase circuits. For example: 100 ft of 12 AWG copper carrying 15 A at 120V — R = 1.98 Ω/1,000 ft = 0.00198 Ω/ft. V_drop = 2 × 100 × 15 × 0.00198 = 5.94 V, or 4.95%.
AC Three-Phase Voltage Drop
V_drop = √3 × L × I × R_per_ft
The multiplier drops from 2 to √3 ≈ 1.732 because in a balanced three-phase circuit the return currents cancel each other in the neutral, reducing the effective conductor length in the calculation. Three-phase systems therefore have lower voltage drop for the same wire gauge and current. This formula assumes unity power factor (resistive loads); inductive loads such as motors have a slightly higher effective impedance.
NEC Voltage Drop Limits and Compliance
The National Electrical Code does not mandate specific voltage drop limits — instead it provides informational notes recommending that conductors be sized so that maximum voltage drop on any branch circuit or feeder does not exceed 3%, and that the combined drop across a feeder plus branch circuit does not exceed 5%. These recommendations appear in NEC 2023 Informational Notes to sections 210.19(A)(1) and 215.2(A)(1). While informational notes are not enforceable requirements, most AHJs (Authorities Having Jurisdiction) treat them as best practice, and many utility companies and equipment manufacturers cite the same thresholds in their specifications.
This calculator flags results with a PASS badge (≤3%), a CAUTION badge (3–5%, acceptable only if feeder drop keeps the total under 5%), or a FAIL badge (>5%, exceeds all NEC recommendations). For critical loads — motors, medical equipment, data centers — target 2% or less.
How to Reduce Voltage Drop in Long Wire Runs
When a calculation shows excessive voltage drop, you have three practical options:
- Increase wire gauge — upsizing one or two AWG sizes is usually the fastest fix. Going from 12 AWG to 10 AWG copper reduces resistance by 37%, cutting drop proportionally.
- Add a subpanel — for runs longer than 100–150 ft to a detached structure (garage, barn, workshop), installing a subpanel at the load end fed by larger feeder conductors is the most cost-effective long-term solution. Check with your Electrical Calculators for wire sizing guidance.
- Increase circuit voltage — converting a 120V circuit to 240V cuts current in half for the same wattage, which halves the voltage drop. This requires a double-pole breaker and a 240V appliance or a step-down transformer at the load.
For underground feeder runs to outbuildings, consult a licensed electrician and your local building department — burial depth, conduit type, and GFCI protection requirements vary by jurisdiction.
Copper vs. Aluminum Conductors
Aluminum wire is roughly 60–65% more resistive per foot than copper of the same AWG. This means an aluminum conductor produces significantly more voltage drop for the same run length and current. However, aluminum costs considerably less per foot and is standard for service entrance conductors (the wires from the utility pole to your panel) and large feeders to subpanels.
When to Use Aluminum
Aluminum makes sense for circuits of 4 AWG and larger where the weight and cost savings are significant — large HVAC feeders, service conductors, and inter-panel feeders. To match the ampacity and voltage drop of copper, aluminum is typically upsized by one or two AWG. For branch circuits in walls and conduit, copper remains the standard because it is easier to terminate and is not subject to the oxidation concerns that apply to aluminum in branch circuit receptacles.
Use the material toggle in the calculator above to compare copper vs. aluminum results for your specific run. For sizing help, see our wire size calculator once available.
Electrical Disclaimer
This calculator provides estimates for informational purposes only and is not a substitute for the advice of a licensed electrician or electrical engineer. Results are based on NEC Chapter 9 formulas and assume ideal conditions — actual voltage drop depends on installation method, ambient temperature, conduit type, conductor bundling, and local code amendments. Always have electrical work designed and inspected by a qualified professional and your local Authority Having Jurisdiction (AHJ). The National Electrical Code is a model code; local jurisdictions may adopt amendments that differ from the values used here.
Sources & References
- NFPA 70: National Electrical Code (NEC) 2023 Edition — National Fire Protection Association